Function Parameter Reference Guide
12.2.109
XMITR1
This prompt is part of the Input 1 Set up group.
This selection lets you instruct the controller to characterize a linear input to represent a
non-linear one.
ATTENTION
Prompt only appears when a linear actuation is selected at prompt IN1TYP.
FOR EXAMPLE:
If input 1 is a 4 to 20 mA signal, but the signal represents a type K thermocouple, select K H and
the controller will characterize the 4 to 20 mA signal so that it is treated as a type K thermocouple
input (high range).
Selections
B
B—B Thermocouple
E H
E H—E Thermocouple High
E L
E L—E Thermocouple Low
J H
J H—J Thermocouple High
J L
J L—J Thermocouple Low
K H
K H—K Thermocouple High
K L
K L—K Thermocouple Low
NNMH
NNMH—Ni-Ni-Moly Thermocouple High
NNML
NNML—Ni-Ni-Moly Thermocouple Low
N90H
N90H—NiMo-NiCo Thermocouple High
N90L
N90L—NiMo-NiCo Thermocouple Low
NIC
NIC—Nicrosil-Nisil Thermocouple
R
R—R Thermocouple
S
S—S Thermocouple
T H
T H—T Thermocouple High
T L
T L—T Thermocouple Low
W H
W H—W5W26 Thermocouple High
W L
W L—W5W26 Thermocouple Low
100H
100H—100 Ohm RTD High
100L
100L—100 Ohm RTD Low
200
200—200 Ohm RTD
500
500—500 Ohm RTD
RADH
RADH—Radiamatic RH
RADI
RADI—Radiamatic RI
LIN
LIN—Linear
SrT
SrT—Square Root