Figure 2-12 Current Output - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Installation
1
+
Controller
-
Load
0 to 750 Ohms
Current
output
4 to 20 mA
24862
See Table 2-3 and Table 2-4 for Control and Alarm Relay Contact
10 Amp Solid State
Relay Assembly
This Solid State relay is rated at 15 Amps at 25°C, linearly derated
1
to 10 Amps at 55°C.
Customer should size fuse accordingly
Figure 2-13 External Solid State Relay Option (Internal Open Collector Output)
16
2
1
5
4
2
3
See Figure 2-15 for Alarm and Duplex Output Connections.

Figure 2-12 Current Output

OUTPUT1 OUTPUT2
White
5-
Black
4+
L2 / N
L1
Green
UDC2300 Controller Product Manual
CAUTION
Installing a current output instrument
into a case wired for relay outputs
will damage the instrument.
Connect shield to ground at one end only.
Set output jumper per Figure 2-2.
information.
10 amp Fast Blo
L1/H
L2/N
LOAD
9-
10+
L2 / N
L1
Green
Black
White
1
AC
-
+
Solid State
Relay
Assembly
24863R
12/00

Hide quick links:

Advertisement

Table of Contents
loading