Honeywell UDC2300 Product Manual page 159

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

12.2.75
RATIO1
This prompt is part of the Input 1 Set up group.
Select the Ratio value you want on Input 1.
Range of Setting: –20.0 to 20.0
12.2.76
RATIO2
This prompt is part of the Input 2 Set up group.
Select the Ratio value you want on Input 2.
Range of Setting: –20.0 to 20.0
12.2.77
RECYCL
This prompt is part of the Setpoint Ramp/Program Set up group.
The recycle number allows the program to recycle a specified number of times from
beginning to end.
Range of Setting: 0 to 99
12.2.78
RLY TY
This prompt is part of the Algorithm Set up group.
RELAY CYCLE TIME INCREMENT selection is used only for Time Simplex and
Duplex output configurations. This configuration sets the increment size of the relay
cycle times in the Tuning Set Up group. The Lockout selection must be set to NONE in
order to view this selection.
Selections
MECH
ELECTROMECHANICAL RELAY—Cycle time in one-second
increments.
S S
SOLID STATE RELAY—Cycle time in 1/3-second increments. This is
useful for solid state relay applications that require shorter cycle times. DO
NOT use this setting unless cycle times of less than 1 second are required.
12/00
(INPUT 1 RATIO)
(INPUT 2 RATIO)
(RECYCLES)
(RELAY CYCLE TIME INCREMENT)