Function Parameter Reference Guide
12.2.49
IN1TYP
This prompt is part of the Input 1 Set up group.
This selection determines what actuation you are going to use for Input 1.
ATTENTION
Changing the input type will result in the loss of Field Calibration values and will restore Factory
Calibration values.
Selections
B
B—B Thermocouple
E H
E H—E Thermocouple High
E L
E L—E Thermocouple Low
J H
J H—J Thermocouple High
J L
J H—J Thermocouple Low
K H
K H—K Thermocouple High
K L
K H—K Thermocouple Low
NNMH
NNMH—Ni-Ni-Moly Thermocouple High
NNML
NNML—Ni-Ni-Moly Thermocouple Low
N90H
N90H—NiMo-NiCo Thermocouple High
N90L
N90L—NiMo-NiCo Thermocouple Low
NIC
NIC—Nicrosil-Nisil Thermocouple
R
R—R Thermocouple
S
S—S Thermocouple
T H
T H—T Thermocouple High
T L
T L—T Thermocouple Low
W H
W H—W5W26 Thermocouple High
W L
W L—W5W26 Thermocouple Low
100H
100H—100 Ohm RTD High
100L
100L—100 Ohm RTD Low
200
200—200 Ohm RTD
500
500—500 Ohm RTD
RADH
RADH—Radiamatic RH
RADI
RADI—Radiamatic RI
0-20
0-20—0 to 20 Milliamperes
4-20
4-20—4 to 20 Milliamperes
10m
10m—0 to 10 Millivolts
50m
50m—0 to 50 Millivolts
0-5
0-5—0 to 5 Volts
1-5
1-5—1 to 5 Volts
0-10
0-10—0 to 10 Volts
100m
100m—0 to 100 Millivolts
138
(INPUT 1 ACTUATION TYPE)
Definitions
UDC2300 Controller Product Manual
12/00

Hide quick links:

Advertisement

Table of Contents
loading