Modbus Read, Write and Override Parameters plus Exception Codes
10.7.9

Options

Table 10-18 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Options.
Parameter
Description
Hex
Auxiliary
0086
Output *
Low Scaling
0031
Factor
High Scaling
0032
Factor
Auxiliary
00EB
Output Range
212
Table 10-17 Set-up Group – Options
Register
Data
Address
Type
Decimal
134
INT
049
FP
050
FP
236
INT
UDC3200 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
0 = None
R/W
1 = Input 1
2 = Input 2
3 = PV
4 = Deviation
5 = Output
6 = Setpoint
7 = LSP
8 = RSP
9 = Input Algorithm 1
R/W
Within the range of the
selected variable in ID 134
R/W
Within the range of the
selected variable in ID 134
0 = 4-20 mA
R/W
1 = 0-20 mA
12/04