Control Set Up Group - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Configuration

4.11 Control Set Up Group

Introduction
The functions listed in this group deal with how the controller will control the process
including: Number of Tuning Parameter Sets, Setpoint Source, Tracking, Power-up
Recall, Setpoint Limits, Output Direction and Limits, Deadband, and Hysteresis.
Function Prompts
Table 4-10 CONTRL Group (Numeric Code 800) Function Prompts
Prompt
English
Numeric
Code
PIDSET
801
SW VAL
802
LSP'S
803
RSPSRC
804
SP TRK
805
PWR UP
806
PWROUT
807
SP Hi
808
SP Lo
809
ACTION
810
36
Description
Number of Tuning
Parameter Sets
Automatic
Switchover Value
Local Setpoint
Source
Remote Setpoint
Source
Setpoint Tracking
Power Up Controller
Mode Recall
TPSC (Three
Position Step
Control) Output
Start-up Mode
Setpoint High Limit
Setpoint Low Limit
Control Output
Direction
UDC2300 Controller Product Manual
Selection or Range of Setting
Numeric
English
Code
0
ONE
1
2KBD (Keyboard)
2
2 PR (PV switch)
3
2 SP (SP switch)
Value in engineering units
within PV or SP range limits
0
ONE
1
TWO
0
NONE
1
INP2
0
NONE
1
PROC (LSP tracks PV–
manual)
2
RSP (LSP tracks RSP–
auto)
0
MAN (Manual/LSP/failsafe)
1
ALSP (Auto/last LSP)
2
ARSP (Auto/last RSP)
3
AMSP (Last mode/last SP)
4
AMLS (Last mode/last LSP)
0
LAST (Last output)
1
FSAF (Failsafe output)
0 to 100 % of the PV range
0 to 100 % of the PV range
0
DIR
1
REV
Factory
Reference
Setting
Guide
Page
ONE
146
0.00
156
ONE
141
NONE
150
NONE
155
MAN
148
LAST
147
2400
153
0
153
REV
120
12/00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents