4.6 SP Ramp Set Up Group

Introduction
A single setpoint ramp [SPRAMP] can be configured to occur between the current local
setpoint and a final local setpoint over a time interval of from 1 to 255 minutes.
SPRATE lets you configure a specific rate of change for any local setpoint change.
You can also configure a 12-segment program from a Ramp/Soak profile.
You can start and stop the ramp/program using the
PV Hot Start is standard and means that at power up, the setpoint is set to the current PV
value and the Ramp or Rate or Program then starts from this value.
Function Prompts
Table 4-5 SPRAMP Group (Numeric Code 300) Function Prompts
Prompt
English
Numeric
Code
SP RAMP
301
TI MIN
302
FINLSP
303
SPRATE
304
EUHRUP
305
EUHRDN
306
SPPROG
307
STRSEG
308
ENDSEG
309
12/00
Description
Selection or Range of Setting
Numeric
Code
Single Setpoint
Ramp
Single Setpoint
Ramp Time
Setpoint Ramp
Final Setpoint
Setpoint Rate
Rate Up
Rate Down
Setpoint
Ramp/Soak
Programming
Start Segment
Number
End Segment
Number
UDC2300 Controller Product Manual
RUN/HOLD
English
0
DIS
1
ENAB
Rate and Program must
be disabled
0 to 255 minutes
Enter a value within the
setpoint limits
0
DIS
1
ENAB
Ramp and Program must
be disabled
0 to 9999 in Engineering
units per hour
0 to 9999 in Engineering
units per hour
0
DIS
1
ENAB
Rate and Ramp must be
disabled
1 to 11
2 to 12 (always end in a
soak segment 2, 4, ... 12)
2
SOK 2
4
SOK 4
6
SOK 6
8
SOK 8
10
SOK 10
12
SOK 12
Configuration
key.
Factory
Setting
DIS
3
1000
DIS
0
0
DIS
- - -
- - -
Reference
Guide
Page
154
156
134
154
133
133
154
156
133
29