Input 2 Set Up Wiring - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Step
Operation
Check the Cold
4
Junction
Temperature
5
Exit the
Calibration Mode

8.6 Input 2 Set Up Wiring

0 to 20 mA or 4 to 20 mA Inputs
• Use the copper leads and connect the calibrator to the rear terminals of Input #2
(see Figure 8-7).
• Make sure jumper at S201 is set for mA (position 1).
See Figure 2-2 Jumper Placements.
Figure 8-7 Wiring Connections for 4 to 20 mA Input – Input 2
12/00
Press
The calculations for zero and span are now stored and you
FUNCTION
will see:
Upper Display = The cold junction temperature at the rear
terminals
Lower Display = CJTEMP (10004)
The value in the upper display is in tenths of a degree. It is
the current reading of the temperature as measured at the
thermocouple terminals and recognized by the controller.
You can change this value, if it is in error, using the
[ ] [ ] keys.
NOTE: The accuracy of the controller is directly affected by
the accuracy of this value. Change this value only if the zero
and span calibration procedures did not bring the controller
within the specified accuracy requirements.
The controller stores the calibration constants and exits the
FUNCTION
calibration mode.
then
DISPLAY
15
+
_
16
Copper
Leads
UDC2300 Controller Product Manual
Result
0 – 20 mA
or
+
4 to 20 mA
_
Source
24878
Input Calibration
91