Configuration

4.4 Timer Set Up Group

Introduction
The Timer Set Up group allows you to configure a time-out period and to select the timer
start by either the keyboard (
also be configured to the start the timer. The timer display is selectable as either "time
remaining" (see TREM) or "elapsed time" (see ET).
Alarm 1 is activated at the end of the time-out period. When the timer is enabled, it has
exclusive control of the alarm 1 relay—any previous alarm 1 configuration is ignored. At
time-out, the timer is ready to be activated again by whatever action has been configured.
Function Prompts
Table 4-3 TIMER Group (Numeric Code 100) Function Prompts
Prompt
English
Numeric
Code
TIMER
101
PERIOD
102
START
103
L DISP
104
RESET
105
INCRMT
106
26
RUN/HOLD
Description
Numeric
Code
Enable or Disable
Timer
Time-out Period
Timer Function
Start
Timer Display
Timer Reset
Control
Timer Count
Increment
UDC2300 Controller Product Manual
key) or Alarm 2. The optional digital input can
Selection or Range of Setting
English
0
DIS
1
ENAB
0:00 to 99:59
Select length of time in
Hours and Minutes, or
minutes and seconds.
0
KEY (
RUN/HOLD
1
AL2 (Alarm 2)
0
TREM (time remaining)
1
ET (elapsed time)
0
Key (Run/Hold key)
1
AL1 (Alarm 1 or Key)
0
MIN (Counts HR/MIN)
1
SEC (Counts MIN/SEC)
Factory
Reference
Setting
Guide
DIS
0:01
key)
KEY
TREM
KEY
MIN
Page
156
145
155
140
156
136
12/00