Three Position Step Output Calibration - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Troubleshooting/Service

9.4 Three Position Step Output Calibration

Three position step control
Three Position Step Control Output Models without Motor Position Indication
(Model Numbers 230B-EE-XX-X0, DC230B-AA-XX-X0)
This model only requires that the "Motor Time" be entered as shown in the calibration
procedure.
Equipment needed
None.
Connections
Apply power and allow the controller to warm up 30 minutes before you calibrate.
Leave all field wiring connected to the rear terminals.
Procedure
The procedure for calibrating the 3 Position Step control output is listed in Table 9-5.
The numeric codes are also listed. Make sure LOCKOUT in Tuning Set Up group is set
to NONE. See Subsection 4.5.
ATTENTION
group function prompt.
Table 9-5 3 Position Step Output Calibration Procedure
Step
Description
Enter Calibration Mode
1
2
Set Motor Traverse
Time
NOTE: This is the time it
takes the motor to travel
from 0 % to 100 %.
Exit the Calibration
3
Mode
100
These prompts only appear when "TPSC" is selected in the algorithm
(Numeric Code 40000)
Press
SET UP
FUNCTION
[ ] [ ]
FUNCTION
DISPLAY
Or
SET UP
UDC2300 Controller Product Manual
Until you see
CAL ( - - - - )
Upper Display =
Lower Display = TPSC (40000)
Until you see
Upper Display = a value
Lower Display = MTR TI (40001)
until the proper motor stroke time is reached (see the
motor specs or measure the time)
Range of setting = 5 to 1800 Seconds
The controller will store the 100 % value.
To exit the calibration mode.
Action
12/00