Operation

6.3 Start Up Procedure for Operation

Table 6-2 Procedure for Starting Up the Controller
Step
Operation
1
Select Manual
Mode
Adjust the Output
2
Tune the
3
Controller
Enter the Local
4
Setpoint
Select Automatic
5
Mode
56
Press
Until "M" indicator is ON.
MAN/AUTO
The controller is in manual mode.
RESET
N/A for Single Display model.
[ ] [ ]
To adjust the output value and ensure that the final control
element is functioning correctly.
Upper Display = Pv Value
Lower Display = OT and the output value in %
Make sure the controller has been configured properly and
SET UP
all the values and selections have been recorder on the
Configuration Record Sheet.
Refer to Tuning Set Up group to ensure that the selections
for PBor GAIN, RATE T, and I MIN, or I RPM have been
entered.
Use Accutune to tune the controller; see the procedure
in this section.
Upper Display = Pv Value
DISPLAY
Lower Display = SP and the Local Setpoint Value
to adjust the local setpoint to the value at which you want
[ ] [ ]
the process variable maintained.
The local setpoint cannot be changed if the Setpoint Ramp
function is running.
Until "A" indicator is ON.
MAN/AUTO
The controller is in Automatic mode.
RESET
The controller will automatically adjust the output to
maintain the process variable at setpoint.
N/A for Single Display model.
UDC2300 Controller Product Manual
Result