Setpoint Rate/Ramp/Program Operation - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

7 Setpoint Rate/Ramp/Program Operation

7.1 Overview
Introduction
The Setpoint Ramp configuration group lets you enable and configure any of the
following:
• SPRATE – a specific rate of change for any local setpoint change. (Subsection 7.2)
• SPRAMP – a single setpont ramp that occurs between the current local setpoint and a
final local setpont over a time interval of 1 to 255 minutes. (Subsection 7.3)
• SPPROG – a ramp/soak profile in a 12-segment program. (Subsection 7.4)
This section explains the operation of each selection and configuration reference where
necessary.
ATTENTION
For any option to function, the other options must be disabled (see Subsection 4.6 –
Configuration).
PV Hot Start
This is a standard feature. At power-up, the setpoint is set to the current PV value and the
Rate or Ramp or Program then starts from this value.
RUN/HOLD key
You can start or stop the Ramp or Program using the RUN/HOLD key.
What's in this section?
The following topics are covered in this section.
7.2 Setpoint Rate
7.3 Setpoint Ramp
7.4 Setpoint Ramp/Soak Programming
12/00
TOPIC
UDC2300 Controller Product Manual
Setpoint Rate/Ramp/Program Operation
See Page
72
72
74
71

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents