Three Position Step Control Algorithm - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

6.11 Three Position Step Control Algorithm

Introduction
The Three Position Step Control algorithm allows the control of a valve (or other
actuator) with an electric motor driven by two controller output relays; one to move the
motor upscale, the other to move it downscale, without a feedback slidewire linked to the
motor shaft.
Estimated Motor Position
The Three Position Step control algorithm provides an output display ("OT") which is an
estimated motor position since the motor is not using any feedback.
• Although this output indication is only accurate to a few percent, it is corrected each
time the controller drives the motor to one of its stops (0 % or 100 %).
• It avoids all the control problems associated with the feedback slidewire (wear, dirt,
and noise).
• When operating in this algorithm, the estimated "OT" display is shown to the nearest
percent (that is, no decimal).
Refer to Subsection 9.4 to set the Motor Travel Time (the time it takes the motor to travel
from 0 % to 100 %).
Motor Position Display
Table 6-14 Procedure for Displaying 3Pstep Motor Position
Step
Operation
Access the
1
Displays
12/00
Press
Until you see:
DISPLAY
Upper Display = PV
Lower Display = OT (The estimated motor position in %)
UDC2300 Controller Product Manual
Result
Operation
67

Hide quick links:

Advertisement

Table of Contents
loading