Honeywell UDC2300 Product Manual page 52

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Configuration
Table 4-13 ALARMS Group (Numeric Code 1100) Function Prompts, continued
Prompt
English
Numeric
Code
AxSxHL
A1S1
1109
A1S2
1110
A2S1
1111
A2S2
1112
AxSxEV
A1S1
1109
A1S2
1110
A2S1
1111
A2S2
1112
ALHYST
1113
ALARM1
1114
BLOCK
1115
42
Description
Numeric
Alarmx Setpoint
State
X = 1 or 2
Alarmx Segment
Event x
X = 1 or 2
Alarm Hysteresis
Latching Alarm
Output
Alarm Blocking
UDC2300 Controller Product Manual
Selection or Range of Setting
English
Code
0
LOW
Low Alarm
1
HIGH
High Alarm
0
BEGN
Beginning of
Segment
1
END
End of Segment
0.0 to 100.0 % of span or
full output as appropriate
0
NO L
1
LACH
0
DIS
Disable Blocking
1
BK1
Block Alarm 1
only
2
BK2
Block Alarm 2
only
3
BK12
Blocks both
Alarms
Factory
Reference
Setting
Guide
Page
HIGH
123
BEGN
123
0.0
121
NO L
120
DIS
126
12/00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents