Ramp time or rate
segments
Ramp unit
Soak segments
Start segment
number
End segment number The end segment number designates the number of the last segment, it must
Recycle number
12/00

Table 7-2 Program Contents

A ramp segment is the time or rate of change it takes to change the setpoint to
the next setpoint value in the program.
• Ramps are odd number segments. Segment #1 will be the initial ramp time.
• Ramp time is determined in either:
TIME* - Hours:Minutes
EU-M* - Degrees/Minute Range = 0 to 999
EU-H* - Degrees/Hour
*The selection of time or rate is made at prompt "RP UNIT"
- Set this prompt before entering any Ramp information.
ATTENTION Entering "0" will imply an immediate step change in setpoint to
the next soak.
The ramp unit selection determines the engineering units for the ramp
segments.
The selections are:
• TIME = Hours:Minutes (XX:XX) Range: 0-99 hr.:0-59 min
• EU-H = Degrees/Hour OR
A soak segment is a combination of soak setpoint (value) and a soak duration
(time).
Soaks are even number segments.
Segment 2 will be the initial soak value and soak time.
The soak setpoint range value must be within the setpoint high and low
range limits in engineering units.
Soak time is the duration of the soak and is determined in:
TIME - Hours:Minutes
The start segment number designates the number of the first segment.
Range = 1 to 11
be a soak segment (even number). Range = 2 to 12
The recycle number allows the program to recycle a specified number of times
from beginning to end. Range = 0 to 99
UDC2300 Controller Product Manual
Setpoint Rate/Ramp/Program Operation
Definition
Range = 0-99 hr.:59 min.
or
EU-M = Degrees/Minute (Range – 0-999)
Range = 0-99 hr.:59 min.
75