Options; Table 10-17 Set-Up Group - Options - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

10.7.9

Options

Table 10-18 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Options.
Parameter
Description
Hex
Auxiliary
0086
Output *
Low Scaling
0031
Factor
High Scaling
0032
Factor
Auxiliary
00EC
Output Range
4/07
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-17 Set-up Group – Options
Register
Data
Address
Type
Decimal
134
INT
049
FP
050
FP
236
INT
UDC2500 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
0 = None
R/W
1 = Input 1
2 = Input 2
3 = PV
4 = Deviation
5 = Output
6 = Setpoint
7 = LSP 1
8 = LSP 2
R/W
Within the range of the
selected variable in ID 134
R/W
Within the range of the
selected variable in ID 134
0 = 4-20 mA
R/W
1 = 0-20 mA
211