4. Set Up and Calibration Procedures - Input Set Up Group

Input Set Up Group

Table 8 lists the parameters and selections available when the SET INPUT group is selected.
On the keypad and local display:
Press the SET UP key to enter the Input Set Up group.
Press the FUNCTION key to scroll through the prompts listed in the set up group.
Press the
Lower Display
Prompt
IN TYP
INP HI
INP LO
FILTYP
LPFILT *
34
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
or
keys to view selections or change range settings.

Table 8 Input Set Up Group Parameters

Upper Display
Selections or
Range of Setting
4-20
0-20
1-5V
0-5V
0-10
R_SP
10.0 to 100
0.0 to 90.0
NONE
SPIK
S+LP
LPAS
[default]
0 to 50.00
(in seconds)
Parameter Definition
INPUT ACTUATION TYPE—This selection specifies the
signal type and range you are going to use for the actuator
input. Be sure that the values configured for the high and low
range, alarm setpoint, etc. are within the measuring range
for the selected signal range.
4 to 20 mA
0 to 20 mA
1 to 5 Volts dc
0 to 5 Volts dc
0 to 10 Volts dc
Remote Setpoint (via communications)
NOTE: Changing the Input Actuation Type will restore the
actuator calibration to its factory values.
INPUT HIGH RANGE VALUE in % is displayed.
INPUT LOW RANGE VALUE in % is displayed.
NOTE: You must set Input Low range to a value that is at
least 10% less than Input High range.
INPUT FILTER TYPE—Allows selection of a software digital
input filter to smooth the input signal.
Spike—Selects spike filter to remove transients in the input
signal when actuator is installed in noisy environments.
Spike plus Low Pass—Selects spike and low pass filtering.
* Allows setting of lag time constant for low pass filter.
Low Pass—Selects low pass filter.
* Allows setting of lag time constant.
NOTE: When Remote Setpoint input type (R_SP) is
selected, input filter type = NONE.
LAG TIME CONSTANT—(Filter Type S+LP or LPAS only)
Allows you to set the first order lag time constant of the low
pass filter when selected. Range is from 0 to 50 seconds.