Loop 1 Tuning Parameters Set Up Group; Table 3-2 Tuning Group Function Prompts - Honeywell DC33XB User Manual

Table of Contents

Advertisement

Configuration

3.3 Loop 1 Tuning Parameters Set Up Group

Function
Prompt
Lower Display
Proportional Band
PROP BD
or
or
Gain
GAIN
or
or
Gain Value being used by
GAINVALn
Gain Scheduling when
enabled
Rate in Minutes
RATE MIN
RSET MIN
Reset in minutes/repeat
or
or
Reset in repeats/minute
RSET RPM
Manual Reset
MAN RSET
Proportional Band 2
PROPBD2
or
or
Gain 2
GAIN 2
RATE2MIN
Rate 2 in Minutes
Reset 2 in minutes/repeat
RSET2MIN
or
or
Reset 2 in repeats/minute
RSET2RPM
Cycle Time (Heat)
CYC SEC
or
CYC SX3
Cycle Time (Cool)
CYC2 SEC
or
CYC2 SX3
SECURITY
Security Code
22

Table 3-2 Tuning Group Function Prompts

Function
Name
UDC3300 Basic Model: DC33XB User Manual
Selections or
Range of Setting
Upper Display
0.1 to 9999%
0.001 to 1000
Read Only
0.00 to 10.00 minutes
0.02 to 50.00
–100 to 100% output
0.1 to 9999%
0.001 to 1000
0.00 to 10.00 minutes
0.02 to 50.00
1 to 120
1 to 120
0 to 4095
Factory
Setting
- -
1.000
- -
0.00
1.00
- -
0
- -
1.000
0.00
1.00
- -
20
20
0
12/00

Advertisement

Table of Contents
loading

This manual is also suitable for:

Udc3300