Local/Remote Switch Locrem; Function Block - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

1MRK 505 394-UEN A
12.4.5
12.4.5.1
Line differential protection RED650 2.2 IEC
Technical manual
Blocking of position indications, BL_UPD. This input will block all inputs
related to apparatus positions for all configured functions within the bay.
Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
The switching of the Local/Remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED, otherwise the default authority level can handle the
control without LogOn. The users and passwords are defined with the IED Users
tool in PCM600.

Local/Remote switch LOCREM

The signals from the local HMI or from an external local/remote switch are
connected via the function blocks LOCREM and LOCREMCTRL to the Bay
control QCBAY function block. The parameter ControlMode in function block
LOCREM is set to choose if the switch signals are coming from the local HMI or
from an external hardware switch connected via binary inputs.

Function block

LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID
IEC05000360-3-en.vsdx
IEC05000360 V3 EN-US
Figure 167:
LOCREM function block
LOCREMCTRL
^PSTO1
HMICTR1
^PSTO2
HMICTR2
^PSTO3
HMICTR3
^PSTO4
HMICTR4
^PSTO5
HMICTR5
^PSTO6
HMICTR6
^PSTO7
HMICTR7
^PSTO8
HMICTR8
^PSTO9
HMICTR9
^PSTO10
HMICTR10
^PSTO11
HMICTR11
^PSTO12
HMICTR12
IEC05000361-3-en.vsdx
IEC05000361 V3 EN-US
Figure 168:
LOCREMCTRL function block
Section 12
Control
IP16319-1 v3
M17086-3 v8
M17088-3 v3