Section 11
Control
11.2.3.3
11.2.3.4
Table 189:
QCBAY Non group settings (basic)
Name
AllPSTOValid
11.2.4
11.2.4.1
11.2.4.2
328
Input and output signals
Table 187:
QCBAY Input signals
Name
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
Table 188:
QCBAY Output signals
Name
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
Setting parameters
Values (Range)
Unit
Priority
-
No priority
Local/Remote switch
Introduction
The signals from the local HMI or from an external local/remote switch are applied
via function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY)
function block. A parameter in function block LOCREM is set to choose if the
switch signals are coming from the local HMI or from an external hardware switch
connected via binary inputs.
Principle of operation
The function block Local remote (LOCREM) handles the signals coming from the
local/remote switch. The connections are seen in figure 167, where the inputs on
function block LOCREM are connected to binary inputs if an external switch is
Type
Default
Description
BOOLEAN
0
External Local/Remote switch is in Off position
BOOLEAN
0
External Local/Remote switch is in Local position
BOOLEAN
0
External Local/Remote switch is in Remote
position
BOOLEAN
0
Data representing the L/R switch position is valid
BOOLEAN
0
Steady signal to block the position updates
BOOLEAN
0
Steady signal to block the command
Type
Description
INTEGER
Value for the operator place allocation
BOOLEAN
Update of position is blocked
BOOLEAN
Function is blocked for commands
BOOLEAN
Local operation allowed
BOOLEAN
Remote operation allowed
Step
Default
-
Priority
1MRK 505 208-UEN B
Description
Priority of originators
Technical reference manual