8.19

CC-Link IE Field Network Diagnostic Function

This function can be used by accessing the engineering tool connected to the CPU module, enabling the detection of a
network error.
(1) How to use the function
The following instructions assume the use of GX Works2 as the engineering tool.
1.
Establish a connection between GX Works2 and the CPU module.
2.
Go to the menu of GX Works2 and start up the CC-Link IE Field Network diagnostics.
[Diagnostics]  [CC IE Field Diagnostics]
1
3
4
5
Item to be diagnosed
Network configuration and error
condition
Display of selected-station
status and error details
Communication Test
IP Communication Test
Cable Test
Link Start/Stop
Network Event History
Reserved Station Function
Enable
Enable/Disable Ignore Station
Errors
System Monitor
Remote Operation
152
Allows the condition of the CC-Link IE Field Network to be checked.
If an error or a warning occurs in the A/D converter module, an icon appears to show the
status of the station.
The communication status of the station selected in "Networks Status" can be checked.
The transient communication route and whether the communication is established from
the connected station to the destination station can be checked.
The reaching time and the route of the IP communication from the connected station to
the target station can be checked.
The cable status between the connected station and the destination station can be
checked.
The network data link can be started and stopped.
The history of various events that occurred in the network can be checked.
A reservation for a station can be temporarily cancelled, and the cancellation can be
disabled. Also, the station numbers for the modules set as reserved stations can be
checked on a list.
A station not set as an error invalid station can be temporarily set as an error invalid
station, and the error invalid station setting can be disabled. Also, the station numbers for
the modules set as (temporarily) error ignore stations can be checked on a list.
The system monitor on the selected station is activated and the status of the module can
be checked.
This function is unavailable for the A/D converter module.
The selected station can be reset through the remote operation.
Description
2
Reference
*1
User's manual for the
master/local module
used
Page 153, Section 8.19
(1) (a)