Appendix 7 Emc And Low Voltage Directives; Measures To Comply With The Emc Directive - Mitsubishi Electric NZ2EX2B-60AD4 User Manual

Cc-link ie field network analog-digital converter module
Table of Contents

Advertisement

Appendix 7
Compliance to the EMC Directive, which is one of the EU Directives, has been a legal obligation for the products sold
in European countries since 1996 as well as the Low Voltage Directive since 1997.
Manufacturers who recognize their products are compliant to the EMC and Low Voltage Directives are required to
attach a "CE mark" on their products.
(1) Sales representative in EU member states
Authorized representative in EU member states is shown below.
Name: Mitsubishi Electric Europe BV
Address: Gothaer Strasse 8, 40880 Ratingen, Germany
Appendix 7.1
The EMC Directive specifies that "products placed on the market must be so constructed that they do not cause
excessive electromagnetic interference (emissions) and are not unduly affected by electromagnetic interference
(immunity)".
This section summarizes the precautions on compliance with the EMC Directive of the machinery constructed with the
module.
These precautions are based on the requirements and the standards of the regulation, however, it does not guarantee
that the entire machinery constructed according to the descriptions will comply with abovementioned directives.
The method and judgement for complying with the EMC Directive must be determined by the person who constructs
the entire machinery.
(1) EMC Directive related standards
(a) Emission requirements
Specification
CISPR16-2-3
Radiated emission
EN61131-2: 2007
CISPR16-2-1, CISPR16-1-2
Conducted emission
*1
QP (Quasi-Peak): quasi-peak value, Mean: mean value
*2
The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a
conductive control panel. The tests were conducted with the module installed in a control panel.
234
EMC and Low Voltage Directives

Measures to comply with the EMC Directive

Test item
Test details
Radio waves from the product are
*2
measured.
Noise from the product to the
*2
power line is measured.
Standard value
• 30M to 230MHz QP: 40dBμV/m (measured over 10m)
• 230M to 1000MHz QP: 47dBμV/m (measured over 10m)
• 150k-500kHz QP: 79dB, Mean: 66dB
• 500k-30MHz QP: 73dB, Mean: 60dB
*1
*1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gf2bn-60ad4

Table of Contents