3.
In "Basic module parameter", set "CH Scaling enable/disable setting" to "0: Enable".
4.
In "Basic module parameter", set the values in "CH Scaling upper limit value" and "CH Scaling
lower limit value".
5.
In "Basic module parameter", set "CH Digital clipping enable/disable setting" to "0: Enable".
6.
Set CH Shifting amount to conversion value (RWw2 to RWw5) to "2000".
When the digital clipping function is used with the scaling function, shift function, and difference conversion function, the
scale conversion, shift addition, and difference conversion are executed on the value after digital clipping.
CHAPTER 8 FUNCTIONS