Main A/D Converter Module - Mitsubishi Electric NZ2EX2B-60AD4 User Manual

Cc-link ie field network analog-digital converter module
Table of Contents

Advertisement

11.2.1

Main A/D converter module

(1) Error code list (0000H to 0FFFH, 1F00H to 1F40H, D529H, D52BH)
The errors are classified into the following three types:
Classification
Major error
Moderate error
Minor error
If any of these errors occur, check that the D LINK LED lights up, and take the corrective actions corresponding to
the error code with the list below.
Error code
Classification
(hexadecimal)
0010H
Major error
010H
Moderate error
*1
Moderate error
0110H
*1
Moderate error
0120H
0130H
Moderate error
0140H
Minor error
0150H
Minor error
0160H
Minor error
This error is a sign that recovery is impossible, with the RUN LED turning off.
This error is a sign that the module cannot continue to operate, with the ERR. LED turning on.
This error is a sign that the module can continue to operate, with the ERR. LED flashing.
Error name
Description and cause
Hardware failure
Module hardware error
The value set in Range setting (address:
Range setting out-
0103H) is out of the range.
of-range
 indicates the number of the channel that has
been incorrectly set.
Non-volatile
memory data error
The non-volatile memory data are abnormal.
(module working
information)
User range data
The value set in the offset/gain setting is
damaged (The
invalid.
channel cannot be
The channel where the error has occurred
identified.)
cannot be identified.
Non-volatile
The parameter data stored in the non-volatile
memory data error
memory are abnormal.
(parameter)
Non-volatile
The error history data stored in the non-volatile
memory data error
memory are abnormal.
(error history)
Incorrect network
Access to A/D converter module when network
parameter access
parameter was in the incorrect status.
error
Remote buffer
A buffer memory area other than the remote
memory access
buffer memory areas has been accessed using
error
the REMFR/REMTO instruction.
CHAPTER 11 TROUBLESHOOTING
Description
Action
Turn off and on the module power supply.
If this error persists, the failure of the module is a
possible cause. Please consult your local
Mitsubishi representative.
Set the value of Range setting (address: 0103H)
within the allowable range.
• Change Module operation information
initialization command (address: 1004H) as
follows: Not commanded (0) → Commanded (1)
→ Not commanded (0). Then, adjust the
module operation information of the non-volatile
memory to the default value.
• Take anti-noise measures including the use of
shielded cables for connection.
• If this error persists, the failure of the module is
a possible cause. Please consult your local
Mitsubishi representative.
Start over the offset/gain setting of all channels
where the user range setting is used.
If an error occurs, please consult your local
Mitsubishi representative.
• Set no request (0), request (1), and no request
(0) in Parameter information clear request
(address: 1002H) and set the parameters of the
non-volatile memory to default.
• Set the parameters again.
• Take measures against noise with a shielded
cable for connection.
• If this error persists, the failure of the module is
a possible cause. Please consult your local
Mitsubishi representative.
• The module will be automatically recovered
immediately after the error occurs. Note that the
error history of the errors that have occurred will
be lost.
• Take measures against noise with a shielded
cable for connection.
• If this error persists, the failure of the module is
a possible cause. Please consult your local
Mitsubishi representative.
Reset network parameter correctly.
Correct the setting data of the REMFR/REMTO
instruction to access the remote buffer memory.
11
173