(3) Voltage input characteristics
The following graph shows the voltage input characteristics.
Digital output
value
No.
Input range setting
1)
-10 to 10V
User range setting 1
(-10 to 10V)
User range setting 2
(-5 to 5V)
2)
0 to 5V
3)
1 to 5V
*1
Set the offset value and gain value in the user range setting within the range satisfying the following conditions.
If the following conditions are not satisfied, A/D conversion may not be properly performed.
<User range setting 1>
• Setting range for offset value and gain value: -10 to 10V
• ((Gain value) - (Offset value)) ≥ 8.0V
• 10.433V ≥ (Gain value - (Offset value × 2))
<User range setting 2>
• Setting range for offset value and gain value: -5 to 5V
• ((Gain value) - (Offset value)) ≥ 4.0V
• 5.21V ≥ (Gain value - (Offset value × 2))
*2
When the analog input value exceeds the range of digital output values, the digital output value is fixed to the maximum
or minimum value.
Input range setting
-10 to 10V
User range setting 1 (-10 to 10V)
User range setting 2 (-5 to 5V)
0 to 5V
1 to 5V
*3
The extension A/D converter module does not support User range 1 and User range 2.
230
Practical analog input range
16383
16000
0
-384
-16000
-16384
-15
-10
-5
Analog input voltage (V)
Offset value
0V
*3
*1
*3
*1
0V
1V
*3
-16384
*3
-384
1)
2)
3)
0 1
5
Gain value
Digital output value
10V
-16000 to 16000
*1
-16000 to 16000
*1
-16000 to 16000
5V
0 to 16000
5V
0 to 16000
Digital output value
Minimum
16383
10
15
*2
Maximum resolution
0.625mV
0.5mV
0.25mV
0.3125mV
0.25mV
Maximum