Mitsubishi Electric NZ2EX2B-60AD4 User Manual page 142

Cc-link ie field network analog-digital converter module
Table of Contents

Advertisement

(4) Setting method (master station)
1.
Set the synchronization period of the master station to either of the following:
• 0.88ms
• 1.77ms
• 3.55ms
For details on the setting method, refer to the following:
When the master station is RJ71GF11-T2 or RJ71EN71:
 MELSEC iQ-R Inter-Module Synchronization Function Reference Manual
When the master station is the simple motion module:
 MELSEC-Q QD77GF Simple Motion Module User's Manual (Positioning Control)
Set the synchronization period of the master station, and "Conversion speed setting" and the number of conversion enabled
channels of the A/D converter modules so that the following conditions are satisfied:
Set value in "Conversion
speed setting"
0: 400μs/channel; or 1:
1ms/channel
2: 100μs/channel
Setting the number of conversion enabled channels beyond the limits shown above results in the error code (0E40H or
1E40H) being stored in Latest error code (RWr0), Error flag (RXA) turning on, and the ERR. LED turning on, with no A/D
conversion performed. In addition, the occurrence of an error (error code: 0E40H or 1E40H) during operation causes the A/D
conversion to be interrupted.
140
Synchronization period of the
master station
0.88ms
1.77ms
3.55ms
• 0.88ms
• 1.77ms
• 3.55ms
Number of conversion enabled channels (maximum)
Main A/D converter module
1
2
4
4
Extension A/D converter
module
1
2
4
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gf2bn-60ad4

Table of Contents