(2) Error code list (D000H to DFFFH (D529H and D52BH excluded))
While any of these errors occurs, the ERR. LED does not turn on. Based on the behavior of the D LINK LED at
the occurrence of an error, the errors are classified into two types, each of which requires different
troubleshooting.
(a) Communication errors where the D LINK LED flashes or turns off
This type of communication error results in the D LINK LED flashing or being turned off. Troubleshoot the
problem with the CC-Link IE Field Network diagnostics. ( Page 152, Section 8.19)
Error code
Error name
(hexadecimal)
D0E0H
Station type mismatch
Own station set to reserved
D0E1H
station
Own station's station number
D0E2H
duplication error
Own station's station number
D0E3H
out-of-range
Station number switch out-of-
D72AH
range (a value other than 1 to
120)
(b) Communication errors where the D LINK LED does not change
This type of communication error results in no change of the D LINK LED. These errors are not shown in CC-
Link IE Field Network diagnostics because they are automatically recovered after the occurrence.
Troubleshooting them requires the error history to be read out. ( Page 168, Section 11.1 (1))
Error code
Error name
(hexadecimal)
Transient data request
D217H
command error
D2A0H
Receive buffer full error
D2A3H
Transient data length error
DF01H
Received transient split error
For two or more errors, only the latest error code is stored in Latest error code (RWr0) or Latest warning code (RWr1).
The errors that have occurred in the past can be checked in the error history of the engineering tool.
For the error history, refer to the following:
• Checking by executing a command of the slave station ( Page 168, Section 11.1 (1))
• Error history data ( Page 222, Appendix 3 (23))
Description and cause
The network parameters are
In the network configuration settings of the master station, change
incorrect or out of the range.
the station type of the module to the remote device station.
• In the network configuration settings of the master station, cancel
The network parameters are
incorrect or out of the range.
• Change the station number of the module to a station number that
• Change the station number avoiding duplication of the station
The settings of the station
number switch are invalid or out
• After taking the above action, power off and on or reset all the
of the range.
The network parameters are
Add the station information of the module to the network
incorrect or out of the range.
configuration settings of the master station.
A station number out of the
Set the station number within the allowable range.
range has been set.
Description and cause
The transient data request
Correct the request command at the transient request source, and
command is incorrect.
execute the command again.
• Check the network status using CC-Link IE Field Network
There is an overload of the
received transient data.
• If the received transient data of the target station is overloaded,
The received transient data is
Correct the number of data (frame length) at the request source, and
incorrect.
retry the execution.
Set the transient data size that the module can accomodate, and
The received transient data is
modify the transient data to the one that is not split. Then send it
split.
again.
CHAPTER 11 TROUBLESHOOTING
Action
the reserved station specification.
is not specified as a reserved station.
number with other stations.
stations where a own station's station number error has been
detected.
Action
diagnostics of the engineering tool to take the appropriate action.
leave the send source for a certain time and try to send the data.
11
177