Functions With The Extension D/A Converter Module Connected - Mitsubishi Electric NZ2EX2B-60AD4 User Manual

Cc-link ie field network analog-digital converter module
Table of Contents

Advertisement

8.18.3
Functions with the extension D/A converter module
connected
With the extension D/A converter module connected, A/D conversion processing of four channels and D/A conversion
processing of four channels is possible.
(1) Available function with the extension D/A converter module connected
Here is the list of the available function with the extension D/A converter module connected:
External power supply monitoring function
(2) Supplementary information related to the connection of the extension D/A
converter module
Here is the list of the supplementary information related to the connection of the extension D/A converter module
for each drive mode:
Drive mode
Normal mode
Trigger conversion mode
Synchronous communication mode
Function
Monitors the on/off state of the external power supply of the extension D/A converter
module, indicating the monitored state by the RUN LED and External power supply READY
flag (RX2F) of the extension D/A converter module. For details, refer to the following:
 CC-Link IE Field Network Digital-Analog Converter Module User's Manual
Supplementary information related to the connection of the
• The conversion speed is fixed to 100μs. The setting of the
conversion speed switch (address: 0001H) is ignored.
• Processing time (100μs) arises in the period from the
completion of conversion processing of each channel to the
start of conversion processing of the next channel.
• The extension D/A converter module operates in trigger output
mode
• The conversion speed is fixed to 100μs. The setting of the
conversion speed switch (address: 0001H) is ignored.
• Processing time (100μs) arises in the period from the
completion of conversion processing of each channel to the
start of conversion processing of the next channel.
• The conversion speed is fixed to 100μs. The setting of the
conversion speed switch (address: 0001H) is ignored.
Description
extension D/A converter module
CHAPTER 8 FUNCTIONS
Reference
Page 93, Section 8.5.1 (3)
Page 87, Section 8.2 (2)
Page 127, Section 8.15
Page 135, Section 8.16
151