(14)CH Time average/Count average/Moving average
This area is used for setting the time average, count average, or moving average for each channel where the
averaging processing is specified.
The following shows the setting range.
*1
Time average
*2
Count average
Moving average
*1
For time average, set a value of (4 × Sampling period) ms or more. A value less than this criterion results in the error
code (020H, 120H) being stored in Latest error code (RWr0), Error flag (RXA) turning on, and the ERR. LED lighting
up. In CH Digital operation value (RWr2 to RWr5, RWr12 to RWr15), 0 is stored.
*2
Setting data other than the above results in the error code (030H and 130H, or 031H and 131H) being stored in
Latest error code (RWr0), Error flag (RXA) turning on, and the ERR. LED lighting up. The A/D conversion processing is
performed with the settings just before the error.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is 0 for all channels.
(c) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
Remote buffer memory name
CH Time average/Count average/Moving
average
● By default, 0 is set and so change the value according to the processing method.
● For the channel where any value is set up, setting the sampling processing results in the set value being ignored.
216
Processing method
*2
0105H
2 to 5000(ms)
4 to 65000 (times)
2 to 128 (times)
Main A/D converter module
CH1
CH2
CH3
0106H
0107H
0108H
Setting value
Extension A/D converter module
CH4
CH1
CH2
0205H
0206H
0207H
CH3
CH4
0208H