(b) With the extension A/D converter module connected
At every synchronization period of the master station, A/D conversion processing of the main A/D converter
module and A/D conversion processing of the extension A/D converter module take place as in the following:
Synchronization cycle
of the master station
Main A/D converter module
A/D conversion of CH1
A/D conversion of CH2
A/D conversion of CH3
A/D conversion of CH4
CH1 Digital operation
value (RWr2)
CH2 Digital operation
value(RWr3)
CH3 Digital operation
value (RWr4)
CH4 Digital operation
value (RWr5)
Extension A/D converter module
A/D conversion of CH1
A/D conversion of CH2
A/D conversion of CH3
A/D conversion of CH4
CH1 Digital operation
value (RWr12)
CH2 Digital operation
value(RWr13)
CH3 Digital operation
value (RWr14)
CH4 Digital operation
value (RWr15)
With an extension analog module connected, normal mode or trigger conversion mode involves processing time (100μs) in
the period from the completion of conversion processing of each channel to the start of conversion processing of the next
channel; however, synchronous communication mode does not involve this processing time.
0.88ms
0
1st A/D conversion value of CH1
1st A/D conversion value of CH2
0
1st A/D conversion value of CH3
0
0
0.88ms
1st A/D conversion value of CH1
0
1st A/D conversion value of CH2
0
1st A/D conversion value of CH3
0
1st A/D conversion value of CH4
0
: Conversion processing (100μs)
1st A/D conversion value of CH4
CHAPTER 8 FUNCTIONS
2nd A/D conversion value of CH1
2nd A/D conversion value of CH2
2nd A/D conversion value of CH3
2nd A/D conversion value of CH4
2nd A/D conversion value of CH1
2nd A/D conversion value of CH2
2nd A/D conversion value of CH3
2nd A/D conversion value of CH4