(b) Averaging processing
1.
Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window  Select the main A/D converter module from "List of stations"
 [CC IE Field Configuration]  [Online]  [Parameter Processing of Slave Station]
2.
In "Basic module parameter", set "CH A/D conversion enable/disable setting" to "0: Enable".
3.
In "Basic module parameter", specify the type of averaging processing for "CH Averaging
process setting".
CH Averaging process setting
4.
In "Basic module parameter", set the value of averaging processing in "CH Time average/Count
average/Moving average".
CH Time average/Count average/Moving
average
For time average, set a value of (4 × Sampling period) ms or more. A value that does not satisfy this condition results in
*1
the error code (020H, 120H) being stored in Latest error code (RWr0), Error flag (RXA) turning on, and the ERR.
LED lighting up. In CH Digital operation value (RWr2 to RWr5, RWr12 to RWr15), 0 is stored.
For the extension A/D converter module, make the settings for each item of "Ext. module 1_Module parameter".
98
Setting item
Selected processing for "CH Averaging
Setting item
1: Time average
2: Count average
3: Moving average
• 1: Time average
• 2: Count average
• 3: Moving average
process setting"
*1
Setting range
Setting range
2 to 5000 (ms)
4 to 65000 (times)
2 to 128 (times)