(20)CH Scaling lower limit value, CH Scaling upper limit value
Set the range of scale conversion for each channel.
For details on the scaling function, refer to the following:
• Scaling Function ( Page 108, Section 8.11)
(a) Setting range
Setting range: -32000 to 32000 (scaling upper limit value > scaling lower limit value)
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is 0 for all channels.
(d) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
Remote buffer memory name
CH Scaling lower limit value
CH Scaling upper limit value
● An error occurs in a channel with a set value out of the range or a set value not meeting the following condition: Scaling
upper limit value > Scaling lower limit value. An error results in the error code (090H and 190H, or 091H and
191H) being stored in Latest error code (RWr0), Error flag (RXA) turning on and the ERR. LED lighting up, resulting
operation just before the error.
● By default, 0 is set and so change the set value.
● With Scaling enable/disable setting (address: 0120H, 0220H) set to Disabled (1), the settings of the following areas are
ignored:
• CH Scaling lower limit value
• CH Scaling upper limit value
220
Main A/D converter module
CH1
CH2
CH3
0121H
0123H
0125H
0122H
0124H
0126H
Extension A/D converter module
CH4
CH1
CH2
0127H
0221H
0223H
0128H
0222H
0224H
CH3
CH4
0225H
0227H
0226H
0228H