Mitsubishi Electric NZ2EX2B-60AD4 User Manual page 23

Cc-link ie field network analog-digital converter module
Table of Contents

Advertisement

No.
Name
PW LED (green)
RUN LED (green)
MODE LED (green)
D LINK LED (green)
ERR. LED (red)
2)
ALM LED (red)
O/G LED (green)
V LED (green),
I LED (green)
CH1 to CH4 LED
(green)
OFFSET LED (green),
GAIN LED (green)
P1
L ER LED (red)
LINK LED (green)
3)
P2
L ER LED (red)
LINK LED (green)
Terminal block for module
4)
power supply and FG
5)
DIN rail hook
Terminal cover
6)
Terminal block for analog
input signals
7)
SET/SEL button
8)
Extension connector cover
Indicates the power supply status of the main A/D converter module.
• On: Power-on
• Off: Power-off
Indicates the operating status of the main A/D converter module.
• On: Operating normally; Writing data to the non-volatile memory (while in offset/gain setting mode)
• Off: Major error occurred
Indicates the mode of the main A/D converter module.
• On: In online mode
• Flashing: In unit test mode
• Off: In offset/gain setting mode
Indicates the data link status of the main A/D converter module.
• On: Data link in operation (cyclic transmission in progress)
• Flashing: Data link in operation (cyclic transmission stopped)
• Off: Data link not performed (disconnected)
Indicates the error status of the main A/D converter module and the extension module.
• On: Moderate error or major error occurred
• Flashing: Warning occurred
• Off: In normal operation
Indicates the alert status of the main A/D converter module and the extension module.
• On: Alert issued
• Flashing: Input signal error detected
• Off: In normal operation
Indicates the module is in offset/gain setting mode.
• On: In offset/gain setting mode
• Off: In a mode other than offset/gain setting mode
Indicates the user range of a set target selected in offset/gain setting mode.
Set target
User range setting 1 (-10 to 10V)
User range setting 2 (-5 to 5V, -20 to 20mA)
Indicates the channel of a set target selected in offset/gain setting mode.
• On: The channel corresponding to the number being on is the set target.
• Off: The channel corresponding to the number being off is not the set target.
Indicates whether the selected setting is offset or gain in the offset/gain setting mode.
Set target
Offset
Gain
PORT1 connector for the connection to CC-Link IE Field Network (RJ45 connector)
Connect an Ethernet cable. ( Page 60, Section 6.5)
There are no restrictions on the connection order of the cables for the P1 connector and P2 connector.
• On: Module received abnormal data, or module performing loopback
• Off: Module received normal data, or module not performing loopback
• On: Link-up
• Off: Link-down
PORT2 connector for the connection to CC-Link IE Field Network (RJ45 connector)
Connect an Ethernet cable. ( Page 60, Section 6.5)
There are no restrictions on the connection order of the cables for the P1 connector and P2 connector.
(same as the LEDs of the P1 connector)
A terminal block for the connection of a module power supply (24VDC) and FG
A hook for mounting a module on a DIN rail
Covers for preventing electric shock while the power is on
A two-piece screw terminal block for the connection to an external device
In offset/gain setting mode, select the set target by pressing  button or  button.
A cover to protect a connector of an extension module. Do not remove the cover if an extension module is not
connected to the connector.
CHAPTER 2 PART NAMES
Application
V LED
I LED
On
Off
Off
On
OFFSET LED
GAIN LED
On
Off
Off
On