Mitsubishi Electric NZ2EX2B-60AD4 User Manual page 241

Cc-link ie field network analog-digital converter module
Table of Contents

Advertisement

The precautions for attaching a noise filter are described below.
• Do not bundle the cables on the input side and output side of the noise filter. If bundled, the output side
noise will be induced into the input side cables from which the noise was filtered.
(power supply side)
Filter
Output side
(device side)
Noise is induced if an input line and an
output line are bundled.
• Ground the noise filter grounding terminal to the control panel with the shortest cable possible (approx.
10cm).
Input side
Input side
(power supply side)
Induction
Arrange the wires with the input lines and
the output lines separated.
Filter
Output side
(device side)
APPX
A
239