(8) Setting procedure
1.
Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window Select a main A/D converter module from "List of stations"
[CC IE Field Configuration] [Online] [Parameter Processing of Slave Station]
2.
In "Station parameter", set "Mode switch" to "1: Trigger conversion mode".
3.
In "Basic module parameter", set "CH A/D conversion enable/disable setting" to "0: Enable".
4.
Click
5.
Check that "0920H" is stored in Latest warning code (RWr1).
[Online] [Monitor] [Device/Buffer Memory Batch]
6.
Turn off and on the module power supply or perform the remote reset to switch the A/D converter
module to trigger conversion mode.
For the extension A/D converter module, make the settings for each item of "Ext. module 1_Module parameter".
134
button to write the parameters to the A/D converter module.