Mitsubishi Electric NZ2EX2B-60AD4 User Manual page 93

Cc-link ie field network analog-digital converter module
Table of Contents

Advertisement

(1) When an extension module is not connected or an extension I/O module is
connected
The sampling period is given by the following:
Sampling period = Conversion speed × Number of conversion enabled channels
Ex.
Assuming that the conversion speed setting is 100μs and the number of conversion enabled channels is
4
Sampling period of the main A/D converter module
100μs
Main A/D converter module
CH1
(conversion enabled
Conversion
channels: CH1 to CH4)
processing
Sampling period of the main A/D converter module = 100μs × 4 = 400μs
(2) When an extension A/D converter module is connected to a main A/D
converter module
When an extension A/D converter module is connected to a main A/D converter module, processing time (100μs)
is generated between the conversion processing of each channel.
(a) With a conversion speed of 100μs
Between the conversion processing (100μs) of each channel, processing time (100μs) is generated. Therefore,
the sampling period is given by the following:
Sampling period = (Conversion speed (100μs) + Processing time (100μs)) × Number of conversion enabled
channels
Ex.
Assuming that the conversion speed setting is 100μs and the number of conversion enabled channels is
4 for both the main A/D converter module and the extension A/D converter module
100μs
Main A/D converter module
CH1
(conversion enabled
Conversion
channels: CH1 to CH4)
processing
Extension A/D converter
CH1
module (conversion enabled
Conversion
channels: CH1 to CH4)
processing
Sampling period of the main A/D converter module = (100μs + 100μs) × 4 = 800μs
Sampling period of the extension A/D converter module = (100μs + 100μs) × 4 = 800μs
100μs
100μs
100μs
CH2
CH3
CH4
Conversion
Conversion
Conversion
processing
processing
processing
Sampling period of the main A/D converter module
100μs
100μs
100μs
CH2
Processing
Conversion
Processing
time
processing
time
Sampling period of the extension A/D converter module
CH2
Processing
Conversion
Processing
time
processing
time
CHAPTER 8 FUNCTIONS
100μs
100μs
100μs
CH1
CH2
CH3
Conversion
Conversion
Conversion
processing
processing
processing
100μs
100μs
100μs
CH3
CH4
Conversion
Processing
Conversion
processing
time
processing
CH3
CH4
Conversion
Processing
Conversion
processing
time
processing
100μs
CH4
Conversion
processing
8
100μs
Processing
time
Processing
time
91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gf2bn-60ad4

Table of Contents