(4) Example of the scaling setting
Ex.
1: For the channel with the set input range of 0 to 5V, of the main A/D converter module, settings are
made as follows:
• "CH Scaling enable/disable setting": "0: Enable"
• "CH Scaling upper limit value": 12000
• "CH Scaling lower limit value": 4000
The digital output value and the digital operation value would be as follows:
Scaling upper limit value
12000
Analog input voltage (V)
0
1
2
3
4
5
110
Digital output value
16000
Scaling lower limit value
4000
0
3200
6400
9600
12800
16000
0
Analog input voltage (V)
0
5
Digital output value
Digital operation value
4000
5600
7200
8800
10400
12000