(7) Warning flag assignment
Assign Warning flag (RX7) to Remote output (RY) of the extension output module using the external signal
assignment function. When a minor error occurs, assigned Remote output (RY) is turned on.
(a) Setting range
With the head of Remote output (RY) of the main A/D converter module as a starting point (0000H), set the
device number for Remote output (RY) of the connected extension output module.
Ex.
When Warning flag (RX7) is assigned to Remote output (RY) numbered 6H as counted from the head
(0H) of the extension output module
Remote output (RY) numbered 6H as counted from the head of the extension output module corresponds
to Remote output (RY) numbered 26H as counted from the head of the main A/D converter module.
Thus, set 26H for Warning flag assignment (address: 0006H).
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is No assignment (FFFFH).
(d) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name
Warning flag assignment
Setting a value out of the range results in the error code (0174H) being stored in Latest error code (RWr0), Error flag (RXA)
turning on, and the ERR. LED lighting up, with the previously set operation.
210
Main A/D converter module
0H
to
1FH 20H
Main A/D converter module
0006H
Extension output module
0H
to
6H
to
FH
to
26H
to
2FH