The data content is 0003H. From the table 1, the inverter stops.
Watch "the current fault type" to "the previous 5 times fault type" of the inverter through commands, the corresponding
function code is P07.27~P07.32 and corresponding parameter address is 071BH~0720H(there are 6 from 071BH).
The command sent to the inverter:
If the response message is as below:
See from the returned data, all fault types are 0023H (decimal 35) with the meaning of maladjustment (STo).
7.3.7.2 Example of writing command 06H
Make the inverter with the address of 03H to run forward. See table 1, the address of "communication control
command" is 2000H and forward running is 0001. See the table below.
The command sent by the master:
If the operation is successful, the response may be as below (the same with the command sent by the master):
Communication protocol
87 - 104