Function
Name
code
Lower limit of
P00.05
the running
frequency
A frequency
P00.06
command
selection
B frequency
P00.07
command
selection
24 - 104
Detailed instruction of parameters
The lower limit of the running frequency is that of the output
frequency of the inverter.
The inverter runs at the lower limit frequency if the set
frequency is lower than the lower limit.
Note: Max. output frequency ≥ Upper limit frequency ≥
Lower limit frequency
Setting range:0.00Hz~P00.04 (Upper limit of the running
frequency)
Note: A frequency and B frequency can not set as the
same frequency given method. The frequency source
can be set by P00.09.
0: Keypad data setting
Modify the value of function code P00.10 to set the
frequency.
1: Analog AI1 setting (correspond to the keyboard
potentiometer)
2: Analog AI2 setting (correspond to AI)
Analog input terminal sets the frequency.
AI2 (0~10V/0~20mA) can be switched by the jumper.
Note: when AI2 selects 0~20mA input, 20mA corresponds to
10V.
100.0% of the analog input corresponds to P00.03, -100.0%
of the analog input corresponds to the reverse P00.03.
6: Multi-step speed running setting
The inverter runs at multi-step speed mode when P00.06=6
or P00.07=6. Set P05 to select the current running stage,
and set P10 to select the current running frequency.
The multi-step speed has the priority when P00.06 or P00.07
does not equal to 6, but the setting stage can only be the
1~15 stage. The setting stage is 1~15 if P00.06 or P00.07
equals to 6.
7: PID control setting
The running mode of the inverter is process PID control
when P00.06=7 or P00.07=7. It is necessary to set P09. The
running frequency of the inverter is the value after PID effect.
See P09 for the detailed information of the preset source,
preset value, feedback source of PID.
8: MODBUS communication setting
The frequency is set by MODBUS communication. See P14
for detailed information.