Salicru CV10-002-S2 User Manual page 57

Controlvit cv10 series
Table of Contents

Advertisement

Function
Name
code
Output upper
P09.09
limit of PID
Output lower
P09.10
limit of PID
Feedback
P09.11
offline
detection value
Feedback
P09.12
offline
detection time
PID adjustment
P09.13
selection
Function Parameters
Detailed instruction of parameters
These parameters are used to set the upper and lower limit
of the PID adjustor output.
100.0 % corresponds to Max. Frequency
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
Set the PID feedback offline detection value when the
detection value is smaller than or equal to the feedback
offline detection value, and the lasting time exceeds the set
value in P09.12, the inverter will report "PID feedback offline
fault" and the keypad will display PIDE.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
0x00~0x11
LED ones:
0: Keep on integral adjustment when the frequency achieves the
upper and low limit; the integration shows the change between the
reference and the feedback unless it reaches the internal integral
limit. When the trend between the reference and the feedback
changes, it needs more time to offset the impact of continuous
working and the integration will change with the trend.
1: Stop integral adjustment when the frequency reaches the upper and low
limit. If the integration keeps stabl e , and the trend between the reference and the
feedback changes, the integration will change with the trend quickl y .
LED tens:
0: Same to the setting direction; if the output of PID
adjustment is different from the current running direction, the
internal control will output 0 forcedly.
1: Opposite to the setting direction
Default
Modify
value
100.0%
0.0%
0.0%
1.0s
0x00
57 - 104