Function
Name
code
UP/DOWN
P08.44
terminals
control setting
UP terminal
P08.45
frequency
changing ratio
DOWN terminal
P08.46
frequency
changing ratio
Action
selection for
P08.47
frequency
settings on
power off
Magnetic flux
P08.50
braking
54 - 104
Detailed instruction of parameters
0x00~0x221
LED ones: frequency enabling selection
0: UP/DOWN terminals setting valid
1: UP/DOWN terminals setting invalid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: All frequency means are valid
2: When the multi-step are priority, it is invalid to the
multi-step
LED hundreds: action selection when stop
0: Setting valid
1: Valid in the running, clear after stop
2: Valid in the running, clear after receiving the stop
commands
0.01~50.00 Hz/s
0.01~50.00 Hz/s
0x000~0x111
LED ones: Action for digital adjustable frequency on power off
0: Save on power off
1: Clear on power off
LED tens: Action for MODBUS frequency setting on power off
0: Save on power off
1: Clear on power off
LED hundreds: Action for other-mode frequency setting on
power off
0: Save on power off
1: Clear on power off
This function code is used to enable magnetic flux.
0: Invalid.
100~150: the bigger the coefficient, the bigger the braking
strength.
This inverter can slow down the motor by increasing the magnetic
flux. The energy generated by the motor during braking can be
transformed into heat energy by increasing the magnetic flux.
The inverter monitors the state of the motor continuously
even during the magnetic flux period. So the magnetic flux
Default
Modify
value
0x000
0.50 Hz/s
0.50 Hz/s
0x000
0
Function Parameters