Salicru CV10-002-S2 User Manual page 50

Controlvit cv10 series
Table of Contents

Advertisement

Function
Name
code
Jogging
P08.07
running ACC
time
Jogging
P08.08
running DEC
time
P08.15
Traverse range
Sudden
jumping
P08.16
frequency
range
Traverse boost
P08.17
time
Traverse
P08.18
declining time
50 - 104
Detailed instruction of parameters
The jogging ACC time means the time needed if the inverter
runs from 0Hz to the Max. Frequency.
The jogging DEC time means the time needed if the inverter
goes from the Max. Frequency (P0.03) to 0Hz.
Setting range:0.0~3600.0s
This function applies to the industries where traverse and
convolution function are required such as textile and chemical fiber.
The traverse function means that the output frequency of the
inverter is fluctuated with the set frequency as its center. The
route of the running frequency is illustrated as below, of
which the traverse is set by P08.15 and when P08.15 is set
as 0, the traverse is 0 with no function.
Traverse range: The traverse running is limited by upper and
low frequency.
The traverse range relative to the center frequency: traverse
range AW=center frequency×traverse range P08.15.
Sudden jumping frequency=traverse range AW×sudden jumping
frequency range P08.16. When run at the traverse frequency, the
value which is relative to the sudden jumping frequency.
The raising time of the traverse frequency: The time from the
lowest point to the highest one.
The declining time of the traverse frequency: The time from
the highest point to the lowest one.
The setting range of P08.15: 0.0~100.0%(relative to the set frequency)
The setting range of P08.16: 0.0~50.0%(relative to the traverse range)
The setting range of P08.17: 0.1~3600.0s
The setting range of P08.18: 0.1~3600.0s
Default
Modify
value
Depends
on model
Depends
on model
0.0%
0.0%
5.0s
5.0s
Function Parameters