Function
Name
code
FDT retention
P08.33
detection value
Frequency
P08.36
arrival
detection value
Energy Braking
P08.37
enable
Energy Braking
P08.38
threshold
voltage
52 - 104
Detailed instruction of parameters
"frequency level detect FDT". Until the output frequency
decreases to a value lower than the corresponding
frequency (FDT retention detection value), the signal is
valid. Below is a diagram:
Setting range of P08.32: 0.00Hz~P00.03 (Max. frequency)
Setting range of P08.33: 0.0~100.0% (FDT electrical level)
When the output frequency is among the below or above
range of the set frequency, the multi-function digital output
terminal will output the signal of "frequency arrival", see the
diagram below for detailed information:
The setting range: 0.00Hz~P00.03 (the Max. frequency)
This parameter is used to control the internal braking unit.
0: Disabled
1: Enabled
Note: Only applied to internal braking unit.
This parameter sets the DC bus voltage above which the internal braking
unit starts to work. Adjust the voltage appropriately to brake the load.
The setting range: 200.0~2000.0V
The recommended setting range: 375~400V
Default
Modify
value
5.0%
0.00Hz
0
380.0V
Function Parameters