Salicru CV10-002-S2 User Manual page 34

Controlvit cv10 series
Table of Contents

Advertisement

Function
Name
code
Motor V/F
P04.03
frequency point
1
Motor V/F
P04.04
voltage
point 1
Motor V/F
P04.05
frequency point
2
Motor V/F
P04.06
voltage point 2
Motor V/F
P04.07
frequency point
3
Motor V/F
P04.08
voltage point 3
34 - 104
Detailed instruction of parameters
torque boost is valid, but over this frequency point, the
torque boost is invalid.
The setting range of P04.01:0.0%:(automatic) 0.1%~10.0%
The setting range of P04.02: 0.0%~50.0%
When P04.00 =1, the user can set V/F curve through
P04.03~P04.08.
V/F is generally set according to the load of the motor.
Note: V1<V2<V3, f1<f2<f3. Too high low frequency
voltage will heat the motor excessively or damage.
Overcurrent stall or overcurrent protection may occur.
The setting range of P04.03: 0.00Hz~P04.05
The setting range of P04.04, P04.06 and P04.08 :
0.0%~110.0% (rated motor voltage)
The setting range of P04.05: P04.03~ P04.07
The setting range of P04.07: P04.05~P02.02 (the rated
frequency of motor)
Default
Modify
value
0.00Hz
00.0%
00.00Hz
00.0%
00.00Hz
00.0%
Function Parameters