example, the function code P00.07 is not stocked into EEPROM. Only by changing the value in RAM can set
the address to 8007H. This address can only be used in writing RAM other than reading. If it is used to read, it is
an invalid address.
7.3.4.2 The address instruction of other function in Modbus
The master can operate on the parameters of the inverter as well as control the inverter, such as running or
stopping and monitoring the working state of the inverter.
Below is the parameter list of other functions
Function
instruction
Communication
control command
The address of the
communication
setting value
SW 1 of the inverter
SW 1 of the inverter
82 - 104
Address
definition
0001H:forward running
0002H:reverse running
0003H:forward jogging
0004H:reverse jogging
2000H
0005H:stop
0006H:coast to stop (emergency stop)
0007H:fault reset
0008H:jogging stop
Communication setting frequency(0~Fmax(unit:
2001H
0.01Hz))
PID reference, range(0~1000, 1000 corresponds
2002H
to100.0% )
PID feedback, range(0~1000, 1000 corresponds
2003H
to100.0% )
Virtual input terminal command , range:
200AH
0x000~0x1FF
Virtual input terminal command , range:
200BH
0x00~0x0F
AO output setting 1(-1000~1000, 1000
200DH
corresponds to 100.0%)
0001H:forward running
0002H:reverse running
2100H
0003H:stop
0004H:fault
0005H: POFF state
Bit0: =0:bus voltage is not established =1:bus
voltage is established
2101H
Bi1~2:=00:motor running
Bit3: =0:asynchronous motor
Data meaning instruction
R/W
characteristics
W/R
W/R
W/R
W/R
W/R
W/R
R
R
Communication protocol