2.1.4 Installation confirmation

Check as followings after the installation:
1. Check that the load range of the input and output cables meet the need of actual load.
2. Check that the accessories of the inverter are correctly and properly installed. The installation cables
should meet the needs of every component (including reactors, input filters, output filters and braking
resistors).
3. Check that the inverter is installed on non-flammable materials and the calorific accessories (reactors
and brake resistors) are away from flammable materials.
4. Check that all control cables and power cables are run separately and the routation complies with EMC
requirement.
5. Check that all grounding systems are properly grounded according to the requirements of the inverter.
6. Check that the free space during installation is sufficient according to the instructions in user's manual.
7. Check that the installation conforms to the instructions in user's manual. The drive must be installed in
an upright position.
8. Check that the external connection terminals are tightly fastened and the torque is appropriate.
9. Check that there are no screws, cables and other conductive items left in the inverter. If not, get them out.

2.1.5 Basic commissioning

Complete the basic commissioning as follows before actual utilization:
1. Restore to the factory parameters (P00.18=1). Then set P02.01 ~ P02.05 (motor data)
2. Adjust the ACC/DEC time according to the actual running of the load.
3. Commission the device via jogging and check that the rotation direction is as required. If not, change the
rotation direction by changing the wiring of motor.
4. Set all control parameters and then operate.

2.2 Product specification

Function
Power input
Power
output
Technical
control
Peripheral
measurement accuracy
interference
8 - 104
Input voltage (V)
Input current (A)
Input frequency (Hz)
Output voltage (V)
Output current (A)
Output power (kW)
Output frequency (Hz)
Control mode
Motor
Adjustable-speed ratio
Overload capability
Key functions
Temperature
Terminal switch input
resolution
Specification
Single-phase 220(-15%)~240(+10%)
Refer to 2.5
50Hz or 60Hz
From 0V to the input voltage (error<5%)
Refer to 2.5
Refer to 2.5
0...400Hz, fluctuation: ±5%
SVPWM (V/f control)
Asynchronous motor
1:100
150% of rated current: 1 minute
180% of rated current: 10 seconds
200% of rated current: 1 second
Stop mode and anti-overtemperature of the bus
Overtemperature point ±3°C
≤ 2ms
Allowed range: 47~63Hz
Product overview