3 Installation Guidelines

The chapter describes the mechanical installation and electric installation.
 Only qualified electricians are allowed to carry out what described in this chapter. Please
operate as the instructions in Safety Precautions. Ignoring these may cause physical
injury or death or damage to the devices.
 Ensure the power supply of the inverter is disconnected during the operation. Wait for at
least the time designated until the POWER indicator is off after the disconnection if the
power supply is applied.
 The installation and design of the inverter should be complied with the requirement of the
local laws and regulations in the installation site. If the installation infringes the
requirement, our company will exempt from any responsibility. Additionally, if users do
not comply with the suggestion, some damage beyond the assured maintenance range
may occur.

3.1 Mechanical installation

3.1.1 Installation environment
The installation environment is the safeguard for a full performance and long-term stable functions of the
inverter. Check the installation environment as followings:
Environment
Installation site
Environment
temperature
Humidity
Storage
temperature
Running environment
condition
12 - 104
Indoor
-10 ~+40 , and the temperature changing rate is less than 0.5 /minute.
If the ambient temperature of the inverter is above 40 , derate 1% for every
additional 1 .
It is not recommended to use the inverter if the ambient temperature is above
50
In order to improve the reliability of the device, do not use the inverter if the
ambient temperature changes frequently.
Please provide cooling fan or air conditioner to control the internal ambient
temperature below the required one if the inverter is used in a close space
such as in the control cabinet.
When the temperature is too low, if the inverter needs to restart to run after a
long stop, it is necessary to provide an external heating device to increase
the internal temperature, otherwise damage to the devices may occur.
RH≤90%
No condensation is allowed.
The maximum relative humidity should be equal to or less than 60% in
corrosive air.
-40 ~+70 , and the temperature changing rate is less than 1℃/minute.
The installation site of the inverter should:
- Keep away from an electromagnetic radiation source
Conditions
Installation Guidelines