Salicru CV10-002-S2 User Manual page 61

Controlvit cv10 series
Table of Contents

Advertisement

Function
Name
code
Overload
pre-alarm of
P11.08
the motor or
the inverter
Overload
P11.09
pre-alarm test
level
Overload
P11.10
pre-alarm
detection time
Function Parameters
Detailed instruction of parameters
The output current of the inverter or the motor is above
P11.09 and the lasting time is beyond P11.10, overload
pre-alarm will be output.
Setting range of P11.08:
Enable and define the overload pre-alarm of the inverter or
the motor.
Setting range: 0x000~0x131
LED ones:
0: Overload pre-alarm of the motor, comply with the rated
current of the motor
1: Overload pre-alarm of the inverter, comply with the rated
current of the inverter
LED tens:
0: The inverter continues to work after underload pre-alarm
1: The inverter continues to work after underload pre-alarm
and the inverter stops to run after overload fault
2: The inverter continues to work after overload pre-alarm
and the inverter stops to run after underload fault
3: The inverter stops when overloading or underloading.
LED hundreds:
0: Detection all the time
1: Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~60.0s
Default
Modify
value
0x000
150%
1.0s
61 - 104

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cv10-004-s2Cv10-008-s2Cv10-015-s2Cv10-022-s2

Table of Contents