Function
Name
code
AVR function
P00.16
selection
Function
P00.18
restore
parameter
P01.00
Start mode
Starting
P01.01
frequency of
direct start-up
Retention time
P01.02
of the starting
frequency
Function Parameters
Detailed instruction of parameters
0: Invalid
1: Valid during the whole prodecure
The auto-adjusting function of the inverter can cancel the
impact on the output voltage of the inverter because of the
bus voltage fluctuation.
0: No operation
1: Restore the default value
2: Clear fault records
Note: The function code will restore to 0 after finishing the
operation of the selected function code.
Restoring to the default value will cancel the user password,
please use this function with caution.
P01 Group Start-up and stop control
0: Start-up directly. Start from the starting frequency
P01.01
1: Start-up after DC braking. Start the motor from the
starting frequency after DC braking (set the parameter
P01.03 and P01.04). It is suitable in the cases where reverse
rotation may occur due to the low inertia load during starting.
Starting frequency of direct start-up means the original
frequency during the inverter starting. See P01.02 for
detailed information.
Setting range: 0.00~50.00Hz
Set a proper starting frequency to increase the torque of the
inverter during starting. During the retention time of the
starting frequency, the output frequency of the inverter is the
starting frequency. And then, the inverter will run from the
starting frequency to the set frequency. If the set frequency is
lower than the starting frequency, the inverter will stop
running and keep in the stand-by state. The starting
frequency is not limited in the lower limit frequency.
Default
Modify
value
1
0
0
0.50Hz
0.0s
27 - 104